Portable Clean Agent Based (SP Type) Fire Extinguisher

AMTEX Brand

Product Overview-Product Features

A clean agent fire extinguisher is a type of gaseous fire suppression. Stored in its liquid form, when it is sprayed and hits the air, it converts to
its gas form which is non-conductive, safe for use while humans are present, leaves no residue, and has a very short atmospheric lifetime,
making it eco-friendly.

The gas, often composed of Halon, extinguishes fire by reducing the oxygen levels and impeding the chain reaction. Because it is non-
conductive and so clean, it is ideal for rooms or businesses filled with electrical and computer equipment. They are most commonly used for class B and C fires.

Safe to use on all your sensitive equipment, the HFC 236fa Clean Agent Extinguisher brings you the added benefit of being the world’s most advanced, and by far the most eco-friendly extinguisher. HFC 236fa Clean Agent Extinguishers leave no residue, pack in mega power and are absolutely safe for use on any sensitive electronic equipment.

AMTEX brand- Clean Agent extinguishers contain HFC 236fa, the cleanest, most powerful extinguishing agent on the planet. They have zero ODP (Ozone Depletion Potential) and are the obvious choice of concerned corporates worldwide. They are extremely lightweight, yet packed with tremendous power and throw, to penetrate past even the finest grills and meshes.

Pressure gauge: Ensure for readiness of working Condition.

World class quality: Comes with ISO 9001 and CE certification, and conforms to ISI standards. Comprehensive Helium Tests and Leak Tests
also guarantee that the products you buy are manufactured according to the world’s most stringent quality standards.

Residue free: It leaves no residue making it safe for use on sensitive equipment .

Lightweight: Extremely

Works on:

Class-A

Class-B

Class-C

Electrically started fires

Technical & Performance Data :

MODEL/MAKEC.A. (S.P.) 2
CAPACITY2KG
EXTINGUISHING AGENTHFC236fa (DU pont-FE36)
PROPELLANTNITROGEN GAS
(As per IS:1747)
APPLICABLE ON FIRESA, B, C, & Electrical Started Fire
OPERATING TEMPERATURE-30 °C to +60 °C
FIRE RATINGMIN 1A& 21B
HYDROSTATIC TEST PRESSURE35 BAR
BURST PRESSUREMIN 55 BAR
WORKING PRESSURE15 BAR
IMPACT TESTPASSED
PRESSURE CYCLING TESTPASSED
TAPPING TESTPASSED
INTERMITTENT DISCHARGE TESTPASSED
COATINGEPOXY POWDER COATING
VALVE / CAP CONSTRUCTIONFORGING AND MACHINING
CAN CONSTRUCTIONDEEP DRAWN AND MIG WELDED
DISCHARGE MECHANISMSQUEEZE GRIP/THUMB TRIGGERED
METHOD OF OPERATIONEASY ACTIVATION
BODY THICKNESSAS PER IS:15683
CAST ANALYSIS OF THE BODYC: 0.25 % max carbon,
S: 0.05 % max
P:0.05%max
of phosphorus)
HELIUM LEAK DETECTION TESTINGYES
LEAKAGE TESTYES
HEIGHT (APPROX.)Approx.350 mm
GROSS WEIGHT (APPROX.)MIN.3.100 Kg
AVERAGE DISCHARGE TIME(MED)MIN 9 SEC
AVERAGE RANGE OF THROW1-2 MTR.
AVERAGE % DISCHARGEMIN 90%
MOUNTING BRACKETYES
PRESSURE GAUGEYES
READYNESS OF WORKINGSHOWING
HOSE ASSEMBLIES(ONLY NOZZLE)
SAFETY LOCKING DEVICEYES(20 N TO 100 N)
CONFORMING STANDARDSIS:15683(LATEST)
NABL LAB APPROVAL
(BI
YES
APPROVALSBIS,CE,EN & ISO
REFILLING SCHEDULEAS PER IS:2190